The MPI-540 meter is designed for checking home and industrial electrical installations. The measurements that can be made, by using the device, provides the results which determine the safety of the installation. In addition, the user has the possibility to register the parameters of electrical networks located at these facilities.
This allows verification of the quality of electricity, and measurement of the parameters of protection against electric shock using a single universal device. Significant automation of measurements of the meter makes possible to test functioning of residual current circuit breakers in the Auto mode, as well as in pre-programmed measuring sequences (so-called auto-tests), which can also be extended with own sequences. Automatic measurement of insulation resistance of 3-, 4- and 5-wire conductors is possible by using additional the AUTO ISO-1000C adapter.
Technical Specifications
Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L
Test current: 23/40 A; measuring range acc. to IEC 61557: 0,13…1999,9 Ω (for 1.2 m test lead):
Display range
Resolution
Accuracy
0,000…19,999 Ω
0,001 Ω
±(5% m.v. + 30 digits)
20,00…199,99 Ω
0,01 Ω
±(5% m.v. + 30 digits)
200,0…1999,9 Ω
0,1 Ω
±(5% m.v. + 30 digits)
rated voltage: 95…270 V (for ZL-PE and ZL-N) and 95…440 V (for ZL-L)
frequency: 45…65 Hz
Measurement of short circuit loop impedance ZL-PE in RCD mode
Test current: 15 mA, measuring range acc. to IEC 61557: 0,50…1999 Ω
Display range
Resolution
Accuracy
0,00…19,99 Ω
0,01 Ω
±(6% m.v. + 10 digits)
20,0…199,9 Ω
0,1 Ω
±(6% m.v. + 5 digits)
200…1999 Ω
1 Ω
±(6% m.v. + 5 digits)
rated voltage: 95…270 V
frequency: 45…65 Hz
Measurement of earth resistance RE with the 3p and 4p method
Measuring range acc. to IEC 61557-5: 0,50 Ω…1,99 k Ω for test voltage 50 V 0,56 Ω …1,99 k Ω for test voltage 25 V
Measurements of RCD parameters (voltage range 95…270 V):
RCD tripping test and measurement of tripping time tA (for tA measurement function)
RCD type
Current
Range
Resolution
Accuracy
General and short-time delay
0,5*IΔn
0…300 ms
1 ms
±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
General and short-time delay
1*IΔn
0…300 ms
1 ms
±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
General and short-time delay
2*IΔn
0…150 ms
1 ms
±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
General and short-time delay
5*IΔn
0…40 ms
1 ms
±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Selective
0,5*IΔn
0…500 ms
1 ms
±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Selective
1*IΔn
0…200 ms
1 ms
±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Selective
2*IΔn
0…200 ms
1 ms
±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Selective
5*IΔn
0…150 ms
1 ms
±(2% m.v. + 2 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
accuracy of residual current application: for 0,5*IΔn:-8…0% for 1*IΔn, 2*IΔn, 5*IΔn: 0…8%
measurement of RCD tripping current IΔn for sinusoidal residual current (AC type)
Rated current
Meas. range
Resolution
Test current
Accuracy
10 mA
3,3…10,0 mA
0,1 mA
0,3 x IΔn…1,0 x IΔn
± 5% IΔn
30 mA
9,0…30,0 mA
0,1 mA
0,3 x IΔn…1,0 x IΔn
± 5% IΔn
100 mA
33…100 mA
1 mA
0,3 x IΔn…1,0 x IΔn
± 5% IΔn
300 mA
90…300 mA
1 mA
0,3 x IΔn…1,0 x IΔn
± 5% IΔn
500 mA
150…500 mA
1 mA
0,3 x IΔn…1,0 x IΔn
± 5% IΔn
1000 mA
330…1000 mA
1 mA
0,3 x IΔn…1,0 x IΔn
± 5% IΔn
the measurement can be started from positive or negative half-period of forced leakage current (AC)
Measurement of RCD tripping current IA for unidirectional residual currentand unidirectional with the 6 mA DC bias (type A)
Rated current
Meas. range
Resolution
Test current
Accuracy
10 mA
3,5…20,0 mA
0,1 mA
0,35 x IΔn…2,0 x IΔn
± 10% IΔn
30 mA
10,5…42,0 mA
0,1 mA
0,35 x IΔn…1,4 x IΔn
± 10% IΔn
100 mA
35…140 mA
1 mA
0,35 x IΔn…1,4 x IΔn
± 10% IΔn
300 mA
105…420 mA
1 mA
0,35 x IΔn…1,4 x IΔn
± 10% IΔn
500 mA
175…700 mA
1 mA
0,35 x IΔn…1,4 x IΔn
± 10% IΔn
measurement for positive or negative half-periods of forced leakage current
Measurement of RCD tripping current I for direct residual current (type B)
Rated current
Meas. range
Resolution
Test current
Accuracy
10 mA
2,0…20,0 mA
0,1 mA
0,2 x IΔn…2,0 x IΔn
± 10% IΔn
30 mA
6…60 mA
1 mA
0,2 x IΔn…2,0 x IΔn
± 10% IΔn
100 mA
20…200 mA
1 mA
0,2 x IΔn…2,0 x IΔn
± 10% IΔn
300 mA
60…600 mA
1 mA
0,2 x IΔn…2,0 x IΔn
± 10% IΔn
500 mA
100…1000 mA
1 mA
0,2 x IΔn…2,0 x IΔn
± 10% IΔn
measurement for positive or negative half-periods of forced leakage current
IΔn – rated residual current
Insulation resistance measurements
Measuring range acc. to IEC 61557-2:
for Un = 50 V: 50 kΩ…250 MΩ
for Un = 100 V: 100 kΩ…500 MΩ
for Un = 250 V: 250 kΩ…999 MΩ
for Un = 500 V: 500 kΩ…2 GΩ
for Un = 1000 V: 1 MΩ…9,99 GΩ
Display range *)
Resolution
Accuracy
0,00…9,99 Ω
0,01 Ω
±(3% m.v. + 8 digits)
10,0…19,9 Ω
0,1 Ω
±(3% m.v. + 8 digits)
20,0…99,9 Ω
0,1 Ω
±(3% m.v. + 8 digits)
20,0…99,9 Ω
0,1 Ω
±(3% m.v. + 8 digits)
20,0…99,9 Ω
0,1 Ω
±(4% m.v. + 6 digits)
*) not greater than measuring range for given voltage
Low-voltage measurement of resistance and circuit continuity Measurement of protective conductor continuity with the ±200 mA current, IEC 61557-4: 0,12…400 Ω
Display range
Resolution
Accuracy
0,00…19,99 Ω
0,01 Ω
±(2% m.v. + 3 digits)
20,0…199,9 Ω
0,1 Ω
±(2% m.v. + 3 digits)
200…400 Ω
1 Ω
±(2% m.v. + 3 digits)
voltage on open terminals: 4…9 V
output current at R < 2 Ω: min. 200 mA
autocalibration of test leads
measurements for both current polarities
Illuminance measurement
Display range
Resolution
Accuracy
0,1…99,9 lx
0,1 lx
±(5% m.v. + 2 digits)
100…999 lx
1 lx
±(5% m.v. + 2 digits)
1,00…9,99 klx
0,01 klx
±(5% m.v. + 2 digits)
10,0…19,9 klx
0,1 klx
±(5% m.v. + 2 digits)
measurement in luxes (lx) or feet-candles (fc)
Three-phase recorder of electrical network parameters
The device is designed to work with networks:
with nominal frequency 50/60 Hz
with nominal voltage:
64/110 V
110/190 V
115/200 V
127/220 V
220/380 V
230/400 V
240/415 V
254/440 V
290/500 V
DC network
Supported networks:
single-phase
two-phase with common N conductor,
three-phase star connection N with and without conductor
three-phase delta
Parameters of analyzer:
Parameter
Measurement range
Max. resolution
Accuracy
Alternating voltage (TRMS)
–
0,0…500 V
0,01 % Unom
±0,5% Unom
Alternating current TRMS
–
depending on clamp*
0,01% Inom
±2% m.v. for m.v. ≥ 10% Inom ±2% Inom for m.v. < 10% Inom (error does not account for clamps error)
Frequency
–
40,00…70,00 Hz
0,01 Hz
±0,05 Hz
Active, reactive, apparent and distortion power
–
depending of configuration (trasformers, clamp)
up to for decimal places
depending of configuration (trasformers, clamp)
Active, reactive apparent energy
–
depending of configuration (trasformers, clamp)
up to for decimal places
as power error
cosφ and power factor (PF
–
0,00…1,00
0,01
±0,03
Harmonics
Voltage
as for alternating voltage
as for alternating voltage
±5% m.v. for m.v. ≥ 3% Unom ±0,15% Unom for m.v. < 3% Unom
Harmonics
Current
as for alternating voltage
as for alternating voltage
±5% m.v. for m.v. ≥ 10% Inom ±0,5% Inom for m.v. < 10% Inom
THD
Voltage
0.0…100.0% (in regards to the rms value)
0,1%
±5%
THD
Current
0.0…100.0% (in regards to the rms value)
0,1%
±5%
Voltage asymmetry
Voltage and current
0,0…10,0%
0,1%
±0,15% (absolute error)
* Clamp F-1A, F-2A, F-3A: 0..3000 A (10000 Ap-p )
* Clamp C-4A: 0..1000 A (3600 Ap-p )
* Clamp C-5A: 0..1000 A (3600 Ap-p )
* Clamp C-6A: 0..10 A (36 Ap-p )
* Clamp C-7A: 0…100 A (360 Ap-p )
MPI-540 Multifunction electrical installations meter WMGBMPI540
$0.00
Description
The MPI-540 meter is designed for checking home and industrial electrical installations. The measurements that can be made, by using the device, provides the results which determine the safety of the installation. In addition, the user has the possibility to register the parameters of electrical networks located at these facilities.
This allows verification of the quality of electricity, and measurement of the parameters of protection against electric shock using a single universal device. Significant automation of measurements of the meter makes possible to test functioning of residual current circuit breakers in the Auto mode, as well as in pre-programmed measuring sequences (so-called auto-tests), which can also be extended with own sequences. Automatic measurement of insulation resistance of 3-, 4- and 5-wire conductors is possible by using additional the AUTO ISO-1000C adapter.
Technical Specifications
Test current: 23/40 A; measuring range acc. to IEC 61557: 0,13…1999,9 Ω (for 1.2 m test lead):
Test current: 15 mA, measuring range acc. to IEC 61557: 0,50…1999 Ω
Measuring range acc. to IEC 61557-5: 0,50 Ω…1,99 k Ω for test voltage 50 V 0,56 Ω …1,99 k Ω for test voltage 25 V
Measuring range acc. to IEC 61557-5: 1 Ω…1,99 kΩ
RCD tripping test and measurement of tripping time tA (for tA measurement function)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
(for RCD with IΔn = 10 mA and 0,5xIΔn uncertainty: ±(2% m.v. +3 digits)
Insulation resistance measurements
Measuring range acc. to IEC 61557-2:
*) not greater than measuring range for given voltage
Three-phase recorder of electrical network parameters
The device is designed to work with networks:
Supported networks:
Parameters of analyzer:
* Clamp F-1A, F-2A, F-3A: 0..3000 A (10000 Ap-p )
* Clamp C-4A: 0..1000 A (3600 Ap-p )
* Clamp C-5A: 0..1000 A (3600 Ap-p )
* Clamp C-6A: 0..10 A (36 Ap-p )
* Clamp C-7A: 0…100 A (360 Ap-p )