MPI-530 meter is a multi-functional instrument for electric shock protection measurements including the option of various methods for measuring earthing and earthing resistance. Additionally the meter enables its user to analyse power supply parameters, records and displays them on its screen. The instrument automatically measures the insulation resistance in a socket and in 3 -, 4 – and 5-wire cables when used with AutoISO-1000C adapter. Measurement results may be continuously verified, depending on user’s demand or according to binding regulations. Memory of the instrument may store tens of thousands of measurements allowing users to store them in a structure of a protocol and describe individual measurement points.
SPECIFICATIONS
Measurement of short circuit loop impedance:
impedance measurement with resolution 0,001 Ω and 23 A current (44 A phase-to-phase) – short-circuit resistor RZW=10 Ω,
measurement range: 95…440 V, frequency 45…65 Hz,
measurement of short circuit loop impedance with resolution 0,01 Ω, in protected systems without tripping the RCD’s with IΔn ≥ 30 mA,
automatic calculation of short-circuit current, differentiating between phase-to-phase and phase-to-neutral voltage,
measurements using UNI-Schuko plug with measurement triggering button (also when L and N leads are exchangeable) or 1,2 m, 5 m, 10 m, 20 m test leads, with optional use of 3-phase socket adapters (AGT),
selection of installation protections and automatic evaluation of measurements results.
Tests of residual current devices (RCD), types AC, A, F, B and B+:
measurement of general, short-time delay and selective RCD’s with rated residual current of 10, 30, 100, 300, 500 and 1000 mA,
automatic measurement of all RCD parameters (when the START button is pressed, the meter performs the whole measurement cycle, including the.
L-PE short circuit loop impedance measurement with 15 mA current),
user selected waveform of forced leakage current: sinusoidal (start from increasing or decreasing edge), unidirectional pulsating (positive or negative), unidirectional pulsating with DC bias (positive and negative), direct (positive and negative),
measurement of tripping current IA using the ramp current,
measurement of tripping time tA at ½IΔn, 1IΔn, 2IΔn and 5IΔn ,
measurement of touch voltage UB and protective conductor resistance RE without the RCD tripping,
detection that L and N conductors are switched in the socket; will not affect the measurement,
measurement of tripping current IA and actual tripping time tAI at single activation of RCD,
measurement for 95…270 V voltage.
Insulation resistance measurements:
test voltage values: 50 V, 100 V, 250 V, 500 V and 1000 V,
insulation resistance measurements up to 10 GΩ,
in-socket measurements using the UNI-Schuko adapter,
meter is protected against voltage on the tested object and voltage appearing during the measurement,
auto-discharge of the object after the measurement,
automatic measurement of all resistance combinations in three-, four- and five core leads using the additional AutoISO-1000C adapter,
acoustic signalling of five-second periods to enable determining the time profile during the insulation resistance measurements.
Low-voltage resistance measurement of equipotential and protective bonding:
continuity measurement of protective conductor with ≥200 mA current in both directions,
low current measurement with sound signal,
autocalibration of test leads – leads of any length can be used.
Earth resistance measurements:
measurement with 3- and 4-pole methods with 2 additional electrodes,
measurement with the 3-pole method with and additional clamp,
measurement with 2-clamp method.
Soil resistivity measurements.
Illuminance measurements.
Quick check of PE connection correctness.
Measurement and recording of voltage, frequency, AC, cosφ and power (active,reactive and apparent), voltage and current harmonics up to 40, THD.
Checking reactive phase sequence and motor direction of rotation.
Innovative memory with possibility of description of: measurement points, facilities, names of customers.
Power supply from rechargeable of disposable batteries (optional)
The meter conforms to EN 61557.
Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L Test current: 23/40 A; measuring range acc. to IEC 61557: 0,13…1999,9 Ω
(for 1.2 m test lead):
Display range
Resolution
Accuracy
0,000…19,999 Ω
0,001 Ω
±(5% m.v. + 0,03 Ω)
20,00…199,99 Ω
0,01 Ω
±(5% m.v. +0,3 Ω)
200,0…1999,9 Ω
0,1 Ω
±(5% m.v. + 3 Ω)
Rated voltage: 95…270 V (for ZL-PE and ZL-N) and 95…440 V (for ZL-L)
Frequency: 45…65 Hz;
Measurement of short circuit loop impedance ZL-PE in RCD mode Test current: 15 mA, measuring range acc. to IEC 61557: 0,50…1999 Ω
Display range
Resolution
Accuracy
0,00…19,99 Ω
0,01 Ω
±(6% w.m. + 10 digits)
20,0…199,9 Ω
0,1 Ω
±(6% w.m. + 5 digits)
200…1999 Ω
1 Ω
Rated voltage: 95…270 V
Frequency: 45…65 Hz
Measurement of earth resistance RE with the 3p and 4p method
Measuring range acc. to IEC 61557 – 5:
0,50 Ω…1,99 kΩ for test voltage 50 V
0,56 Ω…1,99 kΩ for test voltage 25 V
Display range
Resolution
Accuracy
0,00…9,99 Ω
0,01 Ω
±(2% m.v. + 4 digits)
10,0…99,9 Ω
0,1 Ω
±(2% m.v.. + 3 digits)
100…999 Ω
1 Ω
1,00…1,99 kΩ
0,01 kΩ
test voltage: 25 V or 50 V rms
test current: 20 mA, sinusoidal rms 125 Hz (for fn=50 Hz) and 150 Hz (for fn=60 Hz)
measurement blocked at interference voltage UN > 24 V
maximum measured interference voltage Unmax= 100 V
maximum resistance of auxiliary earth electrodes 50 kΩ
Selective earth resistance measurement with clamp (3p + clamp)
Display range
Resolution
Accuracy
0,00…9,99 Ω
0,01 Ω
±(8% m.v. + 4 digits)
10,0…99,9 Ω
0,1 Ω
100…999 Ω
1 Ω
1,00…1,99 kΩ
0,01 kΩ
measurement with additional current clamp
interference current measuring range: up to 9,99 A
Selective earth measurement with two clamps
Display range
Resolution
Accuracy
0,00…9,99 Ω
0,01 Ω
±(10% m.v. + 4 digits)
10,0…99,9 Ω
0,1 Ω
100…999 Ω
±(20% m.v. + 4 digits)
measurement with transmitting and receiving clamps
interference current measuring range: up to 9,99 A
MPI-530 Multifunction Electrical Installation Meter WMGBMPI530
Description
MPI-530 meter is a multi-functional instrument for electric shock protection measurements including the option of various methods for measuring earthing and earthing resistance. Additionally the meter enables its user to analyse power supply parameters, records and displays them on its screen. The instrument automatically measures the insulation resistance in a socket and in 3 -, 4 – and 5-wire cables when used with AutoISO-1000C adapter. Measurement results may be continuously verified, depending on user’s demand or according to binding regulations. Memory of the instrument may store tens of thousands of measurements allowing users to store them in a structure of a protocol and describe individual measurement points.
SPECIFICATIONS
Measurement of short circuit loop impedance:
Tests of residual current devices (RCD), types AC, A, F, B and B+:
L-PE short circuit loop impedance measurement with 15 mA current),
Insulation resistance measurements:
Low-voltage resistance measurement of equipotential and protective bonding:
Earth resistance measurements:
Soil resistivity measurements.
Illuminance measurements.
Quick check of PE connection correctness.
Measurement and recording of voltage, frequency, AC, cosφ and power (active,reactive and apparent), voltage and current harmonics up to 40, THD.
Checking reactive phase sequence and motor direction of rotation.
Innovative memory with possibility of description of: measurement points, facilities, names of customers.
Power supply from rechargeable of disposable batteries (optional)
The meter conforms to EN 61557.
Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L
Test current: 23/40 A; measuring range acc. to IEC 61557: 0,13…1999,9 Ω
(for 1.2 m test lead):
Rated voltage: 95…270 V (for ZL-PE and ZL-N) and 95…440 V (for ZL-L)
Frequency: 45…65 Hz;
Measurement of short circuit loop impedance ZL-PE in RCD mode
Test current: 15 mA, measuring range acc. to IEC 61557: 0,50…1999 Ω
Rated voltage: 95…270 V
Frequency: 45…65 Hz
Measurement of earth resistance RE with the 3p and 4p method
Measuring range acc. to IEC 61557 – 5:
Selective earth resistance measurement with clamp (3p + clamp)
Selective earth measurement with two clamps
Soil resistivity mesurement (ρ)
of RE measurement
Phase sequence indication
Measurements of RCD parameters (voltage range 95…270 V):
RCD tripping test and measurement of tripping time tA (for tA measurement function)
short-time
delay
(for RCD with IΔn=10 mA
and 0,5xIΔn uncertainty:
±(2% m.v. + 3 digits)
accuracy of residual current application: for 0,5*IΔn:-8…0% for 1*IΔn, 2*IΔn, 5*IΔn: 0…8%
Measurement of RCD tripping current IA for sinusoidal residual current (AC type)
current
The measurement can be started from positive or negative half-period of forced leakage current
Measurement of RCD tripping current IA for unidirectional residual current and unidirectional
with the 6 mA DC bias (type A)
current
Measurement for positive or negative half-periods of forced leakage current
Measurement of RCD tripping current IA for direct residual current (type B)
current
Measurement for positive or negative half-periods of forced leakage current
IΔn – rated residual current
Insulation resistance measurements
Measuring range acc. to IEC 61557 – 2:
*) not greater than measuring range for given voltage
Low-voltage measurement of resistance and circuit continuity
Measurement of protective conductor continuity with the ±200 mA current
Illuminance measurement
– – measurement in luxes (lx) or feet-candles (fc)
ANALYSIS AND RECORDING OF SINGLE-PHASE SYSTEM
Current measurement (True RMS)
F-1, F-2, F-3
(C-3, C-6)
±(0,1% In + 2 digits)
(F-1, F-2, F-3)
* the accuracy of current clamps must also be taken into account
Measurement of active power P, reactive power Q, apparent power S and cosφ
[W], [VA], [var]
[W], [VA], [var]
Voltage harmonics measurement
*) from 300 V to 500 V
THD (in relation to the 1 st harmonics)
(h = 2…40)
for URMS ≥ 1% Unom
(h = 2…40)
for IRMS ≥ 1% Inom
NOTE: “m.v.” means “ measured value”
The instruments conforms to: