measurement voltage any in the range of: 50…5000 V (50…1000 V at 10 V and 1…5 kV at 25 V),
continuous indication of measured insulation resistance or leakage current,
automatic discharge of measured object capacitance voltage after the end of insulation resistance measurement,
acoustic signaling of 5 seconds intervals to facilitate capturing time characteristics,
adjustable measuring time to 99’59’’,
metered T1, T2 and T3 test times for measuring one or two absorption coefficients from the range of 1…600 s,
polarization index (PI), absorption coefficients Ab1, Ab2 and dielectric absorption ratio (DAR) measurement,
indication of actual test voltage during measurement,
1.2 mA, 3 mA and 5 mA test current,
insulation resistance measurement using two- or three-wire method,
measurements with test leads up to 20 m…
protection against measuring live objects,
automatic measurement of multiple core cables with the additional AutoISO-5000 adapter
measurement of capacitance during the measurement of RISO.
measurement of temperature (with additional probe – WASONT1),
step voltage insulation resistance measurement (SV),
Dielectric Discharge calculation (DD),
location of damage (burnout),
Digital filters function for measurements in high noise environment.
Continuity measurement of protective connections and equipotential bonding in accordance with EN 61557-4 with current > 200 mA.
Adjustable limits for measured resistance RISO and RCONT.
Measurement of leakage current during insulation resistance testing.
DC and AC voltage measurement in the range of 0…750 V. Drawing graphs on the display during measurement.
Innovative memory with possibility of description of: measurement points, facilities, names of customers.
Operating with mini Bluetooth keyboard (option).
Graphic LCD 5,6’’ backlit.
Keyboard backlit.
Power supply from main power line or battery packs.
Built-in fast charger.
The instruments meet the requirements of the EN 61557 standard.
Insulation resistance measurement
easurement range acc. to IEC 61557-2: UN = 5000 V: 5,00 MΩ …20,0 TΩ
Range
Resolution
Accuracy
0,0…999 kΩ
1 kΩ
±(3% m.v. + 10 digits)
1,00…9,99 MΩ
0,01 MΩ
10,0…99,9 MΩ
0,1 MΩ
100…999 MΩ
1 MΩ
1,00…9,99 GΩ
0,01 GΩ
10,0…99,9 GΩ
0,1 GΩ
100…999 GΩ
1 GΩ
±(3,5% m.v. + 10 digits)
1,00…9,99 TΩ
0,01 TΩ
±(7,5% m.v. + 10 digits)
10,0…20,0 TΩ
0,1 TΩ
±(12,5% m.v. + 10 digits)
Values of measured resistance depending on measurement voltage
Voltage UISO
Measurement
range
AutoISO-5000
measurement range
50 V
200 GΩ
20,0 GΩ
100 V
400 GΩ
40,0 GΩ
250 V
1,00 TΩ
100 GΩ
500 V
2,00 TΩ
200 GΩ
1000 V
4,00 TΩ
400 GΩ
2500 V
10,00 TΩ
400 GΩ
5000 V
20,0 TΩ
400 GΩ
Step voltage insulation resistance measurement
Voltage UISO
MIC-5050
50…1000 V
25 V
1000…5000 V
50 V
Continuity measurement of protective connections and equipotential bonding with 200 mA current
Measurement range acc. to EN 61557-4: 0,12…999 Ω
Range
Resolution
Accuracy
0,00…19,99 Ω
0,01 Ω
±(2%m.v. + 3 digits)
20,0…199,9 Ω
0,1 Ω
200…999 Ω
1 Ω
±(4%m.v. + 3 digits)
Voltage on open terminals: 4…24 V
Output current at R < 15 Ω: min. 200 mA (ISC: 200…250 mA)
Compensation of test lead resistance
Current flowing in both directions, mean value of resistance is displayed
DC and AC voltage measurement
Range
Resolution
Accuracy
0.0…29,9 V
0,1 V
±(2% m.v. + 20 digits)
30,0…299,9 V
0,1 V
±(2%m.v. + 6 digits)
300…750 V
1 V
±(2% m.v. + 2 digits)
Frequency range: 45…65Hz
Measurement of capacitance
Display range
Resolution
Accuracy
1…999 nF
1 nF
±(5%m.v. + 5 digits)
1,00…49,99 µF
0,01 µF
capacity measurement result is displayed after the RISO measurement
for measuring voltages under 100 V capacitance measurement accuracy not specified.
Measurement of temperature
Display range
Resolution
Accuracy
-40,0…99,9 °C
1 °C
±(3%m.v. + 8 digits)
-40,0…211,8 °F
1 °F
±(3%m.v. + 16 digits)
Electrical safety:
type of insulation: double, in acc. with EN 61010-1 and IEC 61557
measurement category: IV 600 V (III 1000 V) in acc. with EN 61010-1
case protection rating in acc. with EN 60529: IP40 (IP67 – with lid closed)
Other technical specifications:
power supply of the meter: built-in battery pack,
weight of the meter: approx. 5,6 kg,
dimensions: 390 x 310 x 180 mm,
display: graphic LCD 5,7′,
transmission of measurement results USB or Bluetooth®.
The acronym “m.v.” stands for a “measured reference value”.
MIC-5050 Insulation Resistance Meter
Description
Insulation resistance measurement: up to 20 TΩ,
Digital filters function for measurements in high noise environment.
Continuity measurement of protective connections and equipotential bonding in accordance with EN 61557-4 with current > 200 mA.
Adjustable limits for measured resistance RISO and RCONT.
Measurement of leakage current during insulation resistance testing.
DC and AC voltage measurement in the range of 0…750 V.
Drawing graphs on the display during measurement.
Innovative memory with possibility of description of: measurement points, facilities, names of customers.
Operating with mini Bluetooth keyboard (option).
Graphic LCD 5,6’’ backlit.
Keyboard backlit.
Power supply from main power line or battery packs.
Built-in fast charger.
The instruments meet the requirements of the EN 61557 standard.
Insulation resistance measurement
easurement range acc. to IEC 61557-2: UN = 5000 V: 5,00 MΩ …20,0 TΩ
Values of measured resistance depending on measurement voltage
range
measurement range
Step voltage insulation resistance measurement
Continuity measurement of protective connections and equipotential bonding with 200 mA current
Measurement range acc. to EN 61557-4: 0,12…999 Ω
DC and AC voltage measurement
Measurement of capacitance
Measurement of temperature
Electrical safety:
Other technical specifications:
The acronym “m.v.” stands for a “measured reference value”.
Related products
MIC-5010 Insulation Resistance Meter
Read moreMIC-10K1 Insulation Resistance Meter
Read moreMIC-5005 Insulation Resistance Meter
Read more