ANALYZER MEASURES AND RECORDS ACCORDING TO THE IEC 61000-4-30 CLASS S STANDARD.
Features:
power to the analyzer is supplied from tested mains (internal power supply) and is used in all types of networks from 64 V to 760 V, with particular emphasis on measurements at low voltage poles, due to the ease of connection,
has an independent power supply socket, especially suited for voltage measurements for transformers and DC circuits,
built-in real-time clock.
Possible measurements:
Measurements according to EN 50160,
Voltage L1, L2, L3,
– average, minimum, maximum and instantaneous values, range to 760 V, ability to work with voltage transformers,
Current L1, L2, L3, N (four inputs),
– average, minimum, maximum and instantaneous values, measurement current with range to 3 kA (depends on used clamp), ability to work with current transformers,
Crest factor for voltage and current,
Frequency from 40 Hz to 70 Hz ,
Active, reactive, distortion, apparent power, including the type of reactive power (capacitive, inductive),
Power recording:
– Budeanu method,
– IEEE 1459,
Active, reactive, apparent energy,
Power factor, cosφ, tgφ,
Up to 40th harmonics for voltage and current,
Total Harmonic Distortion (THD) for voltage and current,
Short-term (PST) and long-term (PLT) flicker,
Unbalance of voltage and current,
Current and voltage events registration including waveforms and RMS graphs half period.
Specification
Range
Resolution
Accuracy
AC
voltage
(TRMS)
–
0.0…760,0 V
0.01 % Un
±0.5% Un
Crest
Factor
Voltage
1.0…10.00
(≤1,65 for
voltage 690 V)
0.01
±5%
Current
1.00…10,00
(≤3,6 Inom)
0.01
± 5% m.v.
AC
current
TRMS
–
depends on
the clamp*
0.01 % of nominal range
±1% of nominal
range
(add clamps
accuracy)
Frequency
–
40.00…70.00 Hz
0.01Hz
±0.05 Hz
Active,
reactive,
apparent
power
and
distortion
–
depends
of configuration
(transformers,
clamp)
up to 4
decimal places
depends
on configuration
(transformers,
clamp)
Active, reactive apparent energy
–
depends
of configuration
(transformers,
clamp)
up to 4
decimal places
the same
as above
cosφ
and Power
Factor (PF)
–
0.00…1.00
0.01
±0.03
tgφ
–
0.00…10.00
0.01
depends on Active
and Reactive
power accuracy
Harmonics
Voltage
same as for AC
voltage TRMS
same as for
AC voltage TRMS
±5% Uh
for Uh ≥ 1% Un
±0,05% Un
for Uh < 1% Un
Current
same as for AC
current TRMS
same as for
AC current TRMS
± 5% Ih
for Ih ≥ 3% In
± 0.15% In
for Ih < 3% In
Total
Harmonics
Distortion
Voltage
0.0..100,0%
0.1%
±5%
Current
±5%
Flicker
–
0.40…10.00
0.01
±10%
Unbalance
Voltage and Current
0.0…10.0%
0.1%
±0.3%
(absolute error)
*Clamp F-1/F-2/F-3:0..3000 A (10000 Ap-p) *Clamp C-4: 0..1000 A (3600 Ap-p)*Clamp C-5: 0..1000 A (3600 Ap-p)*Clamp C-6: 0..10 A (36 Ap-p) (without current transformers) *Clamp C-7: 0…100 A (360 Ap-p )
PQM-700 Power Quality Analyzer WMAUPQM700
Description
ANALYZER MEASURES AND RECORDS ACCORDING TO THE IEC 61000-4-30 CLASS S STANDARD.
Features:
Possible measurements:
– average, minimum, maximum and instantaneous values, range to 760 V, ability to work with voltage transformers,
– average, minimum, maximum and instantaneous values, measurement current with range to 3 kA (depends on used clamp), ability to work with current transformers,
– Budeanu method,
– IEEE 1459,
AC
voltage
(TRMS)
Factor
(≤1,65 for
voltage 690 V)
(≤3,6 Inom)
current
TRMS
the clamp*
range
(add clamps
accuracy)
reactive,
apparent
power
and
distortion
of configuration
(transformers,
clamp)
decimal places
on configuration
(transformers,
clamp)
of configuration
(transformers,
clamp)
decimal places
as above
and Power
Factor (PF)
and Reactive
power accuracy
voltage TRMS
AC voltage TRMS
for Uh ≥ 1% Un
±0,05% Un
for Uh < 1% Un
current TRMS
AC current TRMS
for Ih ≥ 3% In
± 0.15% In
for Ih < 3% In
Harmonics
Distortion
(absolute error)
*Clamp F-1/F-2/F-3:0..3000 A (10000 Ap-p) *Clamp C-4: 0..1000 A (3600 Ap-p)*Clamp C-5: 0..1000 A (3600 Ap-p)*Clamp C-6: 0..10 A (36 Ap-p) (without current transformers) *Clamp C-7: 0…100 A (360 Ap-p )
Related products
PQM-701Z Power Quality Analyzer WMGBPQM701Z
Read morePQM-703 Power Quality Analyzer WMAUPQM703 (Discontinued)
Read morePQM-711 Power Quality Analyzer WMAUPQM711
Read more